Convert resistance to temperature and back for 10K Type II and Type III NTC thermistors and Pt100 or Pt1000 RTDs.
Disconnect the sensor and read its resistance, then compare with the temperature you measure next to it. If the two disagree by more than a few degrees, check the curve type, wiring resistance and the controller input setting before replacing the sensor.
Estimates based on your inputs. Always verify against the manufacturer's data and the codes that apply where you work.
Describe the symptom and your readings. Brixon helps you work through the free, quick checks first, then the deeper tests. It can be wrong, so confirm on the equipment.
Ask Brixon, first question free